Near-Infrared Off-Axis Integrated Cavity Output Spectroscopic Sensor System for Ammonia Leakage Measurement in Cold Store Using Embedded Multi-Core Processor
Ying Hua,Lei Zhang,Yishen Zhou,Ling Yu,Kaiyuan Zheng,Fang Song,Mingshi Liu,Yue Yang,Chuantao Zheng,Yiding Wang
DOI: https://doi.org/10.1016/j.infrared.2024.105150
IF: 2.997
2024-01-13
Infrared Physics & Technology
Abstract:A near-infrared off-axis integrated cavity output spectroscopic (OA-ICOS) sensor system for ammonia (NH 3 ) leakage detection was developed. A distributed feedback (DFB) laser was used to target the absorption line of NH 3 at 6612.167 cm -1 . Experiments were conducted to evaluate the performance of the sensor system. When the averaging time is 0.8 s, the detection limit (1σ) of NH 3 is ∼ 1.21 parts-per-million by volume (ppmv) using wavelength modulation spectroscopy (WMS). The 10–90% response time of the NH 3 sensor system is ∼ 7.2 s. Based on the developed local monitoring and control platform (LMCP), cloud server, remote monitoring and control end (RMCE), the unattended NH 3 leakage detection experiments were carried out in a cold store located in Jilin City. The experimental results confirmed the rapid detection capability of the reported sensor system for NH 3 leakage as well as the capability of remote monitoring and control.
optics,physics, applied,instruments & instrumentation