Space charge drift from a +/- 400-kV direct current transmission line

R C Hendrickson
DOI: https://doi.org/10.1002/bem.2250070404
Bioelectromagnetics
Abstract:The Minnesota Environmental Quality Board completed a 3-year study of the space charge plume outside the right of way of a bipolar (+/- 400 kV) direct current transmission line in rural west central Minnesota. The purpose of the study was to determine the levels of DC potential gradient and small airs ions in the downwind plume to which humans and animals may be exposed. Potential gradient measurements show that a space charge plume is detectable downwind at least 1600 m from the transmission line. Plume relaxation rates indicate that under certain conditions one could detect the plume at twice that distance or more. Net charge in the plume assumes the polarity of the downwind energized transmission line conductor. The bipolar DC line thus electrically bisects the land through which it passes; on one side of the line there is a net positive space charge, on the other side a net negative space charge. Electric charge in the plume resides on aerosols and small air ions. Polar conductivity data substantiate the fact that small air ions of one polarity in the plume are elevated while those of opposite polarity are suppressed compared to background concentrations found in the rural environment. The resulting charge imbalance persists downwind at least 1600 m, though the median small air ion concentrations of plume polarity have adjusted to within the background range by that time with perpendicular wind speed components between 1 and 6 m/sec.