Study on the Inhibition Effect of C6F12O on Charged Particles in the Flame of Transformer Oil Discharge Gas

Shuang S. Tian,Zhe Li,Chen Y. Li,Xiao X. Zhang
DOI: https://doi.org/10.1080/00102202.2024.2306303
IF: 1.9
2024-01-21
Combustion Science and Technology
Abstract:The accidental combustion of insulating oil poses a significant risk in the event of transformer failure. The charged particles generated through the combustion ionization reaction exert considerable influence on the combustion speed and stability of the flame. Therefore, the detailed chemical reaction mechanism including neutral matter and charged particle is simplified. The two-dimensional finite rate reaction model is established. The theoretical calculation investigates the suppressive effect of the novel fire extinguishing agent C 6 F 12 O on charged particles in the flame resulting from transformer oil decomposition. The analysis encompasses changes in flame temperature, free radicals, and charged particles in the decomposition gas of transformer oil under C 6 F 12 O concentrations ranging from 0% to 4%. The findings reveal that the addition of C 6 F 12 O exerts a discernible inhibitory effect on the flame temperature of the transformer oil exhaust gas. The large reduction of charged particles in the flame caused by C 6 F 12 O is achieved by its consumption of large amounts of O and OH radicals in the flame. It hampers key elementary reactions responsible for charged particle generation. In conclusion, C 6 F 12 O demonstrates a pronounced inhibitory effect on charged particles in the flame resulting from transformer oil decomposition.
energy & fuels,engineering, chemical,thermodynamics, multidisciplinary
What problem does this paper attempt to address?