Rapid Admittance Measurement of Power Converters Using Double-PLL Grid-Following Inverters

Weihua Zhou,Mohammad Hasan Ravanji,Nabil Mohammed,Behrooz Bahrani
DOI: https://doi.org/10.1109/tpwrd.2024.3363762
IF: 4.825
2024-01-01
IEEE Transactions on Power Delivery
Abstract:The increasing use of inverter-based resources (IBRs) in power systems highlights the need for a deep understanding of their stability and dynamics. Traditional analytical models, limited by the black-box nature of IBRs, underscore the importance of frequency-domain methods through measured admittance. Facing challenges in real-world admittance measurement, such as the absence of ideal voltage or current sources, the use of measurement inverters as perturbation sources has emerged as a promising approach, despite drawbacks like reduced system stability and increased measurement time. This article introduces a novel control strategy for measurement inverters, elucidating the impact of abc/dq and dq/abc transformations on admittance measurement. The key advancements are an analysis of the admittance contributions from these transformations and the implementation of double phase-locked loops in the measurement inverters, aimed at improving stability and decreasing measurement duration.
engineering, electrical & electronic
What problem does this paper attempt to address?