Development of a 500kV PPLP MI cable system for HVDC applications

Sung-yun Kim,E. Jung
Abstract:LS Cable & System already developed HVDC ±250kV mass-impregnated type kraft cable system with a conductor cross-section of 900 mm flexible joints and outdoor terminations in 2008. This HVDC submarine cable system was successfully established between Jindo and Jeju island in Korea. Based on this experience, a HVDC 500kV PPL paper MI cable system, including land joint and outdoor-termination, was developed by LS Cable & System. In order to prove the mechanical and electrical performances for this system, a type test was carried out according to CIGRE recommendations. A full scale cable system has been tested successfully. And additional load cycle and polarity reversal tests on the cable system showed a higher performance compared with a similar mass impregnated paper cables.
Physics,Engineering
What problem does this paper attempt to address?