Modelling and cooling power control of a TES-backed-up vapour-compression refrigeration system

D. Rodríguez,G. Bejarano,M. Vargas,J. M. Lemos,M. G. Ortega
DOI: https://doi.org/10.1016/j.applthermaleng.2019.114415
2024-02-07
Abstract:This work addresses the modelling, power control, and optimization of a thermal energy storage (TES) system combined with a vapour-compression refrigeration facility based on phase change materials (PCM). Given a novel design of a PCM-based TES tank and its interconnection with an existing refrigeration system, the joint dynamic modelling is first studied, exploring the different time scales that coexist at the interconnected system. Diverse operating modes are defined, according to the intended use of the TES tank as a cold-energy buffer to decouple cooling demand and production, whereas the static characteristic and power limits are calculated and show the high coupling between the main cooling powers involved (TES charging/discharging power, and direct power production at the evaporator). In this light, a decoupling control strategy is proposed, where the low-level controllers are simply PI regulators and the refrigerant/secondary mass flows are considered as virtual manipulated variables, applying a feedforward-based cascade strategy. The control performance is evaluated through a thorough simulation that includes all operating modes, where the reference tracking is shown to be fast and reliable enough to address high-level scheduling strategies, where the references on the main cooling powers are intended to be imposed considering economic and efficiency criteria.
Systems and Control
What problem does this paper attempt to address?
### Problems Addressed by the Paper The paper primarily explores the combined modeling, power control, and optimization of thermal energy storage (TES) systems incorporating phase change materials (PCM) with vapor compression refrigeration systems. #### Main Research Content 1. **System Modeling**: The study investigates the combined dynamic modeling of PCM-based thermal energy storage tanks and existing refrigeration systems, analyzing the dynamic characteristics of the system at different time scales. 2. **Operation Mode Definition**: Various operation modes are defined based on the different uses of the TES tank as a cold energy buffer, and the static characteristics and power limits are calculated. 3. **Decoupling Control Strategy**: A decoupling control strategy is proposed, controlling the mass flow rates of the refrigerant and secondary fluid through a low-level PI controller and a feedforward cascade strategy. 4. **Simulation Verification**: Detailed simulations verify the control performance, demonstrating the speed and reliability of reference tracking, capable of handling high-level scheduling strategies. #### Background and Motivation - Globally, refrigeration and freezing consume a significant amount of energy, especially in industrial, commercial, and household applications. - Improving the energy efficiency of vapor compression refrigeration systems has both economic and environmental value. - Integrating thermal energy storage systems into refrigeration systems can achieve cold energy management and optimize refrigeration power production, thereby improving energy efficiency and economic costs. #### Technical Details - The system is designed with a TES tank containing PCM, which works in parallel with the existing vapor compression refrigeration system. - PCM maintains a constant temperature during the energy storage process, improving heat exchange efficiency. - Through detailed system modeling and control strategy design, efficient energy management is achieved. The paper aims to enhance the overall performance and energy efficiency of refrigeration systems through comprehensive modeling and advanced control strategies.