MARTINI: Smart Meter Driven Estimation of HVAC Schedules and Energy Savings Based on WiFi Sensing and Clustering

Kingsley Nweye,Zoltan Nagy
DOI: https://doi.org/10.1016/j.apenergy.2022.118980
2021-10-18
Abstract:HVAC systems account for a significant portion of building energy use. Nighttime setback scheduling is an energy conservation measure where cooling and heating setpoints are increased and decreased respectively during unoccupied periods with the goal of obtaining energy savings. However, knowledge of a building's real occupancy is required to maximize the success of this measure. In addition, there is the need for a scalable way to estimate energy savings potential from energy conservation measures that is not limited by building specific parameters and experimental or simulation modeling investments. Here, we propose MARTINI, a sMARt meTer drIveN estImation of occupant-derived HVAC schedules and energy savings that leverages the ubiquity of energy smart meters and WiFi infrastructure in commercial buildings. We estimate the schedules by clustering WiFi-derived occupancy profiles and, energy savings by shifting ramp-up and setback times observed in typical/measured load profiles obtained by clustering smart meter energy profiles. Our case-study results with five buildings over seven months show an average of 8.1%-10.8% (summer) and 0.2%-5.9% (fall) chilled water energy savings when HVAC system operation is aligned with occupancy. We validate our method with results from building energy performance simulation (BEPS) and find that estimated average savings of MARTINI are within 0.9%-2.4% of the BEPS predictions. In the absence of occupancy information, we can still estimate potential savings from increasing ramp-up time and decreasing setback start time. In 51 academic buildings, we find savings potentials between 1%-5%.
Systems and Control,Machine Learning
What problem does this paper attempt to address?
The problem this paper attempts to address is: how to use existing smart meter and WiFi data to estimate actual occupancy in buildings and, based on this, develop effective HVAC (Heating, Ventilation, and Air Conditioning) schedules to achieve energy savings. Specifically, the paper proposes a method called MARTINI, which derives typical occupancy schedules and energy-saving potential by clustering occupancy information derived from WiFi and energy consumption data from smart meters. The goal of MARTINI is to reduce unnecessary energy consumption by adjusting the start and setback times of the HVAC system without compromising indoor comfort. ### Main Issues 1. **Lack of Actual Occupancy Information**: Traditional HVAC energy-saving measures typically rely on standard occupancy schedules or the experience of facility managers, which cannot accurately reflect the actual occupancy of buildings. 2. **Challenges in Energy-Saving Potential Assessment**: Before or after implementing energy-saving measures, it is necessary to assess the potential energy-saving effects. Traditional methods such as field experiments and Building Energy Performance Simulation (BEPS) are costly and complex. 3. **Feasibility of Large-Scale Application**: A scalable method is needed that can utilize the widely available smart meter and WiFi infrastructure, suitable for a large number of buildings. ### Solution - **MARTINI Method**: - **Data Collection**: Collect occupancy information and energy consumption data from WiFi connection logs and smart meter data. - **Preprocessing**: Clean, transform, and aggregate the data to generate building-level occupancy and energy consumption time series. - **Clustering Analysis**: Use the KMeans algorithm to cluster daily occupancy and energy consumption profiles to determine representative occupancy schedules and energy consumption profiles. - **Scheduling and Energy-Saving Estimation**: Adjust the start and setback times of the HVAC system based on the occupancy schedules and estimate the energy-saving potential. - **Validation**: Use the WinAM building energy performance simulation software to validate the accuracy of the energy-saving estimates. ### Experimental Results - **Case Study**: Experiments were conducted in 51 buildings at the University of Texas at Austin, with WiFi connection data available for 5 buildings. - **Energy-Saving Effects**: The average energy-saving rate in summer ranged from 8.1% to 10.8%, and in autumn from 0.2% to 5.9%. - **Validation**: The average energy-saving rate estimated by MARTINI differed from the BEPS predicted value by 0.9% to 2.4%. ### Conclusion The MARTINI method provides a low-cost, non-intrusive way to estimate actual occupancy in buildings using existing smart meter and WiFi data, and to develop effective HVAC schedules based on this, achieving significant energy savings. This method has broad application prospects, especially in commercial buildings.