Towards energy savings from a bimodal occupancy driven hvac controller in practice

Nan Li
2013-01-01
Abstract:Energy consumption in commercial buildings amounts to 19% of total energy consumption in the U.S., and is expected to continue increasing in the foreseeable future. Heating, Ventilation, and Air Conditioning (HVAC) systems are major energy consumers in commercial buildings, and they are usually controlled in a way that all thermal zones in a building are considered as occupied during operational hours. This control strategy, however, results in energy waste by conditioning the unoccupied thermal zones. This paper employs a bimodal demand response controller, which is based on real-time occupancy, for reducing HVAC energy consumption. The controller employs an artificial neural network based occupancy detection model to monitor occupancy in thermal zones of a building, and controls HVAC based on real-time occupancy to save energy while maintaining occupant thermal comfort. Based on real-time occupancy and time of the day, the proposed controller operates the HVAC system in three modes: occupied mode, vacant mode, and off-hour mode, each with distinct temperature settings. During the three weeks of the test, the occupancy model yielded an occupancy detection accuracy of up to 93.6%, providing reliable support to the occupancy driven HVAC controller. The daily percentage energy savings varied between -0.2% and 14.4%, with an average of 5.3%. Higher daily energy savings were observed in days when the building was less occupied. Outside temperature was found to be linearly correlated with the daily energy savings.