Loss Induced Maximum Power Transfer in Distribution Networks

Matthew Deakin,Thomas Morstyn,Dimitra Apostolopoulou,Malcolm McCulloch
DOI: https://doi.org/10.48550/arXiv.1710.07787
2017-10-21
Abstract:In this paper, the power flow solution of the two bus network is used to analytically characterise maximum power transfer limits of distribution networks, when subject to both thermal and voltage constraints. Traditional analytic methods are shown to reach contradictory conclusions on the suitability of reactive power for increasing power transfer. Therefore, a more rigorous analysis is undertaken, yielding two solutions, both fully characterised by losses. The first is the well-known thermal limit. The second we define as the `marginal loss-induced maximum power transfer limit'. This is a point at which the marginal increases in losses are greater than increases in generated power. The solution is parametrised in terms of the ratio of resistive to reactive impedance, and yields the reactive power required. The accuracy and existence of these solutions are investigated using the IEEE 34 bus distribution test feeder, and show good agreement with the two bus approximation. The work has implications for the analysis of reactive power interventions in distribution networks, and for the optimal sizing of distributed generation.
Optimization and Control,Systems and Control
What problem does this paper attempt to address?