Low-voltage AC series arc fault location method based on RBF neural network

Quanyi Gong,Qun Gao,Xiaohui Qu,Ke Peng,Liang Feng,Chuanliang Xiao
DOI: https://doi.org/10.1016/j.epsr.2024.110176
IF: 3.818
2024-02-03
Electric Power Systems Research
Abstract:In recent years, the safety of civil electricity has been seriously affected by low-voltage AC series arc faults. However, for indoor distribution lines (220 V/50 Hz), only a few researchers pay attention to the research of AC series arc fault location. Therefore, a fault location method of low-voltage AC series arc based on RBF neural network is proposed. Firstly, a fast and highly accurate frequency estimation algorithm based on the union of amplitude-phase is proposed to redundant calculations and errors arising from the Fast Fourier Transform (FFT) process are reduced. The proposed method extracts the voltage and current signals in the 0∼3 kHz frequency band. The current amplitude difference per meter of the line is calculated. However, influenced by the dynamic arc resistance, the minor differences no longer correspond to the actual fault point. The arc fault location model is trained by integrating the RBF neural network, and the deviation is eliminated. The performance of the model has also been verified in a variety of operating conditions with actual measurement data. The results show that the established localization model is generic and can be applied to complex indoor cable scenarios.
engineering, electrical & electronic
What problem does this paper attempt to address?