New correlation features for dissolved gas analysis based transformer fault diagnosis based on the maximal information coefficient

Yongliang Liang,Zhongyi Zhang,Ke‐Jun Li,Yu‐Chuan Li
DOI: https://doi.org/10.1049/hve2.12136
IF: 4.967
2021-08-16
High Voltage
Abstract:Online monitoring of gases dissolved in transformer oil is widely applied. Improving the performance of dissolved gas analysis (DGA)-based fault diagnosis methods by exploring new features of time-series data has become an appealing topic. In this study, a new type of correlation features between characteristic gases was extracted from time-series data based on the maximal information coefficient (MIC), and a fuzzy inference system was established. After the introduction of the principle of the MIC and a method for calculating the MIC-based correlation features, the dominant symptom features that can be used to classify fault types were extracted through the receiver operating characteristic curve. Then, fuzzy rules were learnt, and a fuzzy inference system was designed. In addition, to improve the feasibility of the method, the Newton interpolation method was used for adaptation to the existing sampling cycle. The diagnostic results of the test data show that the proposed method has excellent performance and outperforms some prevailing traditional rule-based methods as well as some artificial intelligent methods. The results also show that by exploring new correlation features from time-series data based on the MIC, the performance of DGA-based methods can be improved.
engineering, electrical & electronic
What problem does this paper attempt to address?