Optimized Autonomous Operation Control to Maintain the Frequency, Voltage and Accurate Power Sharing for DGs in Islanded Systems

Li Sun,Kai Sun,Yunhe Hou,Jiabing Hu
DOI: https://doi.org/10.1109/tsg.2020.2992802
IF: 10.275
2020-09-01
IEEE Transactions on Smart Grid
Abstract:Most of the launched power electronics-enabled distributed generators (DGs) adopt phase-locked-loop (PLL) synchronization control. In this paper, we delve into two different autonomous operation control (AOC) strategies to ensure the frequency/voltage profile and accurate power sharing for such DGs in islanded systems. The commonly used AOC is based on the concept of active power-frequency ( $P-f$ ) and reactive power-voltage magnitude ( $Q-V$ ) droop and deployed in a decentralized way. It is frequently criticized for inaccurate reactive power sharing between DGs, subject to the mismatch in their output impedances. To cope with this issue, we first design a local AOC using the $P-f$ and $Q-dot {V}$ (i.e., the time derivate of $V$ ) droop concept, where the desired reactive power sharing can be achieved at the expense of a marginal and allowable $V$ excursion. Then, we develop an optimization-based AOC that is implemented through a continuous-time alternating direction method of multipliers (ADMM) algorithm and neighborhood communication. Equilibrium analysis and local asymptotic stability of the proposed AOC strategies are both established using a Lyapunov method. Finally, simulations are carried out in two islanded systems to validate the improvement in power sharing under a wide range of possible system conditions.
engineering, electrical & electronic
What problem does this paper attempt to address?