Flexibility of Commercial Building HVAC Fan as Ancillary Service for Smart Grid

Mehdi Maasoumy,Jorge Ortiz,David Culler,Alberto Sangiovanni-Vincentelli
DOI: https://doi.org/10.48550/arXiv.1311.6094
2013-11-24
Systems and Control
Abstract:In this paper, we model energy use in commercial buildings using empirical data captured through sMAP, a campus building data portal at UC Berkeley. We conduct at-scale experiments in a newly constructed building on campus. By modulating the supply duct static pressure (SDSP) for the main supply air duct, we induce a response on the main supply fan and determine how much ancillary power flexibility can be provided by a typical commercial building. We show that the consequent intermittent fluctuations in the air mass flow into the building does not influence the building climate in a human-noticeable way. We estimate that at least 4 GW of regulation reserve is readily available only through commercial buildings in the US. Based on predictions this value will reach to 5.6 GW in 2035. We also show how thermal slack can be leveraged to provide an ancillary service to deal with transient frequency fluctuations in the grid. We consider a simplified model of the grid power system with time varying demand and generation and present a simple control scheme to direct the ancillary service power flow from buildings to improve on the classical automatic generation control (AGC)-based approach. Simulation results are provided to show the effectiveness of the proposed methodology for enhancing grid frequency regulation.
What problem does this paper attempt to address?