Stability analysis and singular perturbation model reduction of DFIG-based variable-speed pumped storage unit adopting the fast speed control strategy

Xiaoqiang Tan,Chaoshun Li,Dong Liu,He Wang,Xueding Lu,Zhiwei Zhu,Rongli Xu
DOI: https://doi.org/10.1016/j.est.2024.111340
IF: 9.4
2024-03-31
Journal of Energy Storage
Abstract:Stable operation is critical for variable-speed pumped storage units (VSPSUs) to play a regulatory role in the grid. Simplified models can be used to study the stability of the pump-turbine governor system for VSPSU. However, electrical factors are often oversimplified, which can affect the accuracy of the established model. The main focus of this work is small-signal stability analysis and model reduction of the VSPSU. Firstly, an integrated high-order model of VSPSU with a fast speed control strategy is established. Then, the stability of VSPSU is evaluated by analyzing the stable domain of the governor control parameters. The results indicate that the parameter factors have an obvious coupling effect on system stability. The pump-turbine characteristics have distinct opposing effects on system stability when water head and speed are increased, respectively. To simplify the stability analysis studies, a new reduced-order model of VSPSU is derived using the singular perturbation method. The proposed 6-order reduced-order model, which incorporates a slow subsystem and boundary layer system, exhibits high precision in stable domain calculations and rotational speed dynamic simulations. A key electrical factor affecting the accuracy of the VSPSU reduced-order model is the stator resistance R s .
energy & fuels
What problem does this paper attempt to address?