Testing research on AC interference of UHV AC gil test line to buried metal pipeline

B. Zhou,Y. Qiu,N. Li,H.-g. Liu,J. Zhang,Hui-Chun Xie
DOI: https://doi.org/10.1049/icp.2022.0221
Abstract:There may be circulating current in a GIL system through vertical ground wires, grounding grids, and enclosure. In addition, there may also be abnormal conditions such as equipment fault. These will cause AC interference to the buried underground pipelines nearby. Based on electrified examination for the UHV AC GIL test line, buried metal pipelines were laid in parallel near GIL, and the test platform of GIL for AC interference to buried pipelines was built. The on-site pipelines, monitoring coupons, test piles, and reference electrodes were buried. The effect of enclosure leakage current on the electrochemical corrosion of adjacent metal pipelines during GIL's long-term operation was investigated. The various parameters were on-site measured at intervals. The test results show that: after the current is applied to GIL, AC interference occurs in the pipeline and soil. Before and after the current was applied to GIL, the pipeline to ground potential has almost no change. The corrosion degree of buried coupons is very slight. Generally, the degree of AC interference is very slight and can be almost ignored.
Environmental Science,Engineering
What problem does this paper attempt to address?