Fault characteristics analysis of DFIGWT in whole LVRT process considering control strategy switching between RSC and Crowbar

Fan Xiao,Yongjun Xia,Kanjun Zhang,Zhe Zhang,Xianggen Yin
DOI: https://doi.org/10.1016/j.ijepes.2022.108615
2023-02-01
Abstract:In order to address the relaying protection issues of the full renewable energy grid, the fault characteristics of the DFIGWT in whole LVRT process should be studied. Currently, researches on fault characteristics of DFIGWT considering crowbar generally assume that crowbar is activated at the moment of fault. However, in fact, the DFIGWT’s fault current characteristics are mainly affected by both (rotor-side converter) RSC and crowbar. The crowbar does not act instantaneously at the moment of fault due to the control system. The DFIGWT is mainly controlled by the RSC before the crowbar is activated. In this paper, the fault process was divided into two stages, namely RSC control stage and crowbar activating stage. The fault characteristics of DFIGWT were analyzed at RSC control stage. Then, the activation time of crowbar was obtained, especially the activation of crowbar due to over-voltage of DC bus was considered. The last values of stator and rotor flux linkages at the first stage were calculated and used as the initial values of the stator and rotor flux linkages at the second stage. Then, the analytical expressions of rotor flux linkage were deduced by Laplace and inverse Laplace transformations. Based on this, the fault mechanism of DFIGWT is resolved and analytical expression of DFIGWT’s short circuit characteristics considering whole LVRT process was proposed. The expression of DFIGWT’s fault current characteristics was verified by the simulation results.The research results are helpful to the construction of relaying protection system for a full-renewable-based system.
engineering, electrical & electronic
What problem does this paper attempt to address?