Statistical Analysis of Wildfire Accidents Inducing Flashover of Transmission Lines
Yun ZHANG,Fei YOU,Hai-xiang CHEN,Lin-he ZHANG,Ji-ping ZHU,Jian-jun ZHOU
DOI: https://doi.org/10.3969/j.issn.1009-0029.2011.12.025
2011-01-01
Fire Science and Technology
Abstract:Based on the statistics of some flashover of transmission lines induced by wildfire and the field survey of typical burned area,fire frequency and flashover ratio,geographical information of fire region,brief status of wildfire and flashover accidents were analyzed,the types,evolution process,influencing factors,and property parameters of potential wildfires,and the discharge characteristics of transmission lines were explored.Results show that ground fires,crown fires,red crown fire and crown fire converted from ground fires are easy to lead to the flashover of transmission lines.Most fires are upswept and easy to ambient conditions prone to induce flashover as high flame height,high thermal output,high temperature and high concentration(smoke particles and electric mass points).The discharge happens mainly at subconductors,main discharge patterns are conductor-to-tree,conductor-to-conductor and conductor-to-ground.Under conditions of wildfires with medium and high intensities,the discharge distances can exceed the safe air gaps for normal operation,this can form stream with large amounts of charged mass points to bring flashover.