Simulation and performance assessment of a heat pump coupled to a sub-slab thermal storage system

Luminita Dumitrascu,Ian Beausoleil-Morrison
DOI: https://doi.org/10.1080/23744731.2023.2299172
2024-01-20
Science and Technology for the Built Environment
Abstract:The paper explores the performance of a sub-slab ground heat exchanger, coupled to a heat pump, and the ability of the system to provide space conditioning and domestic hot water (DHW) for a multi-unit residential building (MURB) located in Ottawa, Ontario. The parametric analysis conducted to optimize the design of the building, as well as the sensitivity analysis performed to optimize the configuration of the sub-slab ground heat exchanger is also presented. According to the simulated results, the ground layer can store some of the rejected energy over medium term, without reducing the long-term performance of the heat pump. The annual energy consumption per dwelling unit (including heat pump, all auxiliary equipment, appliances, and lights) was estimated to be 28.4 GJ, significantly lower than the average annual energy consumption for a low-rise apartment in Canada (46.7 GJ per apartment). To assess the sensitivity of the system to environmental conditions, the simulation was conducted using the weather files for other five locations in Canada.
engineering, mechanical,thermodynamics,construction & building technology
What problem does this paper attempt to address?