Experimental study on the cross-infection control performance under intervention cascade ventilation in the post-epidemic era

Han Li,Yuer Lan,Zhaoying Wang,Xiangfei Kong,Man Fan
DOI: https://doi.org/10.1016/j.scs.2024.105185
IF: 11.7
2024-01-25
Sustainable Cities and Society
Abstract:The ventilation system plays a key role in maintaining a healthy environment in an enclosed space. To seek a reasonable air distribution method and improve indoor air quality, the air change efficiency, exposure risk and infection risk under heating conditions are explored in a comparative experimental study under ICV, stratum ventilation (SV) and mixing ventilation (MV). The results demonstrate that with the same amount of air (94 l/s) and designed room temperature (22 °C), the air change efficiency of ICV is 9.8 % and 24.3 % higher than SV and MV, indicating the excellent ability to form a clean and healthy breathing layer. During the pandemic, ICV can reduce the infection risk of COVID-19 by 5 % and 22.1 % in four hours relative to SV and MV. Exposure risk distribution research results demonstrate that ICV can maintain a reduction in exposure level of 9.64–44.44 % even at a location farther from the air inlet and provide a safer environment where people sit frequently. The conclusions obtained in this study can provide a new approach for ventilation to address COVID-19 and indoor air quality problems during heating season.
energy & fuels,construction & building technology,green & sustainable science & technology
What problem does this paper attempt to address?