Energy load analysis according to environmental control strategy of partially applied electrochromic smart window

Seung-Hoon Han,Jae-Hyang Kim
DOI: https://doi.org/10.1080/13467581.2024.2356261
IF: 0.904
2024-05-25
Journal of Asian Architecture and Building Engineering
Abstract:The percentage of energy consumed by buildings is very large in industry. Recently, the cases of applying smart technology to efficiently improve the energy waste of these buildings are increasing, and this study targets Electrochromic (EC) smart windows. Smart window means a window that can freely change Visible Light Transmittance (VLT) and Solar Heat Gain Coefficient (SHGC). Since windows are the largest medium that can cause energy loss in buildings, the application of smart windows enables efficient energy management. However, this technology currently has a high-cost problem, so a partial application to windows is proposed. This study aims to analyze the relationship between partially applied smart windows and energy loads. Smart windows require an environment control strategy because windows are primarily to provide a comfortable indoor environment. An environmental control strategy was established according to the application area of the smart window, and Useful Daylight Illuminance (UDI) was used. In addition, the energy load of the smart window in which the environmental control strategy was established was derived, and the relationship with the partially applied area was analyzed. This study provides information on how much the partial application of smart windows can save energy wastage in buildings.
construction & building technology
What problem does this paper attempt to address?
The paper attempts to address the issue of reducing building energy consumption through the partial application of electrochromic (EC) smart windows while minimizing installation costs. Specifically, the study aims to analyze the relationship between the partial application of EC smart windows and energy loads, and to explore how to reduce air conditioning and heating energy consumption while ensuring the quality of the indoor lighting environment. ### Research Background 1. **Building Energy Consumption Issues**: - According to the 2018 energy consumption statistics published by the International Energy Agency (IEA) in 2020, the final energy consumption of the residential and service sectors in South Korea accounts for approximately 31% of the total consumption, and CO2 emissions account for 33%. - The energy consumption required for building maintenance has a significant impact on the entire industry, especially under warm and humid climate conditions, where reducing energy loss and consumption through windows or building envelopes becomes particularly important. 2. **Smart Window Technology**: - Smart windows can control indoor lighting and heat by adjusting the visible light transmittance (VLT) and solar heat gain coefficient (SHGC), thereby achieving efficient energy management. - Currently, the cost of smart window technology is relatively high, so a partial application of smart windows is proposed. ### Research Objectives and Methods 1. **Research Objectives**: - To explore whether reducing the installation area of EC smart windows can still effectively improve the indoor lighting environment and reduce energy loads while minimizing installation costs. - To analyze the impact of different installation areas of EC smart windows on the indoor lighting environment and energy loads. 2. **Research Methods**: - **Model Setup**: The study object is a south-facing office space with model dimensions of 20,000 mm × 6,000 mm × 3,000 mm. The application ratios of EC smart windows are 100%, 75%, 50%, 25%, and 0%. - **UDI Simulation Setup**: Useful Daylight Illuminance (UDI) analysis is based on the LEED v4.1 standard, with simulation times on sunny days during the equinoxes, solstices, and the time range from 9:00 to 18:00. - **Cooling and Heating Load Simulation Setup**: Energy load analysis is conducted using the EnergyPlus engine, with simulation times on sunny days during the equinoxes and solstices, analyzing the impact of SHGC changes on energy loads. ### Main Results 1. **UDI Results**: - When the application ratio of EC smart windows is 75%, the UDI satisfied area ratio is between 60% and 94%, maintaining a good indoor lighting environment for most of the time. - When the application ratio is 100%, the UDI satisfied area ratio is between 75% and 89%, consistently maintaining a good indoor lighting environment. 2. **Cooling and Heating Load Results**: - During the equinox, as the application ratio of EC smart windows increases, the energy load gradually increases. - During the summer solstice, as the application ratio of EC smart windows increases, the energy load gradually decreases, with a maximum energy-saving effect of 26.01%. ### Conclusion Through simulation analysis, this study verifies the effectiveness of partially applying EC smart windows in reducing building energy consumption. It is recommended that, where cost permits, the application ratio of EC smart windows be set at 75% to achieve significant energy savings while ensuring the quality of the indoor lighting environment.