Refrigerant charge distribution in brine-to-water heat pump using R290 as refrigerant

Luis Sánchez-Moreno-Giner,Timo Methler,Francisco Barceló-Ruescas,José Gonzálvez-Maciá
DOI: https://doi.org/10.1016/j.ijrefrig.2022.10.013
IF: 4.14
2023-01-01
International Journal of Refrigeration
Abstract:This paper presents experimental results from a brine-to-water heat pump used for space heating at low temperature, with a low refrigerant charge of R290 (propane). Performance and refrigerant distribution were analysed in every test condition studied. Performance results show a declared heating capacity of 9.5 kW , obtaining a specific capacity ( C c ) of 48.7 kW rm kg − 1 and a seasonal coefficient of performance of 4.01. In terms of refrigerant distribution, at the nominal point, 41.5% of the refrigerant is located in the compressor, mainly dissolved in the oil, and the rest is separated almost evenly in both heat exchangers, 23.9% in the condenser and 27.8% in the evaporator; having the lines and accessories (pneumatic-ball valves) the remaining 6.8%. Due to this fact, reducing oil solubility by heating the crankcase or increasing the superheat (SH) has a positive impact on the refrigerant charge reduction, but it also affects the coefficient of performance.