Frequency Response Output Control Strategy of Electrochemical Energy Storage Participating in Day-Ahead Joint Dispatch of Power Grid
Rao Liu,Yannan Chang,Huaiyuan Liu,Yiwen Sun,Fuzeng Bao,Zehua Shen,Xiaoyu Zhou
DOI: https://doi.org/10.1109/CEEPE58418.2023.10166183
2023-05-12
Abstract:Aiming at the problem that the day-ahead joint dispatch with electrochemical energy storage (EES) considering frequency security involves too many virtual control parameters of EES and these values need to be optimized, an equivalent simplified frequency response output control strategy of EES is developed for to reduce the complexity of programming and solving. Through analytical calculation, it is clear that the integrated control strategy including virtual inertia and virtual droop can be replaced by the virtual droop control individually that reaches the same frequency nadir, so the virtual inertia response coefficient is not taken as the frequency response control parameter of EES; Through the simulation analysis, it is found that the improvement of the overall frequency response capability of the system is not obvious and the frequency response capability of the unit is inhibited by reducing the primary frequency regulation dead zone of EES, and the primary frequency regulation dead zone is not used as the adjustable control parameter of EES; Finally, a practical frequency response control strategy of EES on the grid side in day-ahead dispatch is proposed, which realizes the equivalent adjustment effect to the complex control with multiple parameters through only virtual droop control, so as to reduce the variables to be optimized and the complexity of model solution in day-ahead joint dispatch problem.
Environmental Science,Engineering