On the Degradation Mechanism of Low-Voltage Underground Cable with Poly(Vinyl Chloride) Insulation

H. M. Tawancy,M. Hassan
DOI: https://doi.org/10.1007/s11665-016-2109-1
IF: 2.3
2016-05-11
Journal of Materials Engineering and Performance
Abstract:A study has been undertaken to determine the degradation mechanism leading to localized short-circuit failures of an underground low-voltage cable with PVC insulation. It is shown that that the insulation of outer sheath and conductor cores has been cracked by thermal degradation involving dehydrochlorination, oxidation, and loss of plasticizers leading to current leakage between the cores. Most evidence points out that overheating due to poor connection of copper wires as well as a chemically active soil has caused the observed degradation.
materials science, multidisciplinary
What problem does this paper attempt to address?