Dynamic process modeling and converter parameter optimization of marine based pulsed power system
LU Qiuyu,ZHENG Jianping,YANG Yinguo,YU Zhen,LIU Yang,XUE Yicheng,ZHANG Zheren,XU Zheng
DOI: https://doi.org/10.16081/j.epae.202210013
2023-01-01
Abstract:In the new-type power systems,the grid-forming non-synchronous machine sources can lose transient stability with the synchronous generator(SG). Therefore,an analytical method for transient stability of receiving system with grid-forming modular multilevel converter(MMC) is proposed. The grid-forming MMC is modeled as the current source and voltage source respectively during the fault and after the fault.Based on the model,the analytical calculation method of the critical clearing angle and critical clearing time is illustrated. According to the proposed analytical method,the influence of several critical factors on the system transient stability are analyzed,including the MMC injected current amplitude and phase angle,fault locations,load power sharing between the SG and MMC. Based on the PSCAD/EMTDC,the built electromagnetic transient simulation model verifies the effectiveness,accuracy and robustness of the proposed analytical method.