Abstract:In this paper, a new pilot protection scheme for AC line connected to LCC-HVDC inverter based on composite-mode model is proposed. First, taking commutation failure into consideration, 1-mode and 2-mode equivalent instantaneous models of inverter in different operating conditions are built. Second, according to the equivalent instantaneous inductances of inverter in different combinations of operating conditions, the equivalent models of inverter are summarized into 4 operation states. Then, the 1-mode and 2-mode equivalent models are combined to establish the composite-mode model of AC/DC hybrid system. And then, using multi-time section information, the instantaneous inductances of backside composite-mode model are calculated. Thus, protection criterion is constructed on the difference between composite-mode models of in-zone faults and that of out-of-zone faults for fault locating. Finally, RT-LAB simulation tests show that, the proposed method offers high sensitivity and reliability, unaffected by commutation failure.
engineering, electrical & electronic
What problem does this paper attempt to address?