Numerical study of hydrogen leakage dispersion and explosion of a 2 × 120 kW PEM fuel cell integrated power station

Wenhao Zhang,Min Liu,Yi Xiao,Qiliang Wu,Jiawei Wang,Tao Wang,Yongsheng Zhang
DOI: https://doi.org/10.1016/j.ijhydene.2024.01.300
IF: 7.2
2024-02-01
International Journal of Hydrogen Energy
Abstract:In recent years, numerous integrated hydrogen projects have been carried out around the world, but the characteristics of hydrogen leakage and deflagration in complex spaces are unknown. This paper simulates the spatiotemporal evolution of hydrogen leakage in a kW-scale hydrogen fuel cell-integrated power station. In this study, the concentration of hydrogen leakage was strongly influenced by the ventilation conditions in complex closed spaces. At 804 s after the leak, the volume and the hydrogen concentration of the combustible hydrogen cloud, in natural ventilation, were 22.35 % and 75.67 % of those in a closed space, respectively. Ventilation conditions also affect the ignition of the combustible hydrogen cloud, the overpressure, and the temperature after ignition. The overpressure value in natural ventilation is only 24 % of the value in a closed space. This research provides some effective suggestions for the safety risk assessment of a kW-scale hydrogen fuel cell-integrated power station.
energy & fuels,electrochemistry,chemistry, physical
What problem does this paper attempt to address?