Compatibility Issues With Irregular Current Injection Islanding Detection Methods in Multi-DG Units Equipped With Grid-Connected Transformers

Menghua Liu,Wei Zhao,Qing Wang,Zhiming Wang,Caijun Jiang,Jie Shu,Hao Wang,Yu Bai
DOI: https://doi.org/10.1109/tpel.2021.3117879
IF: 5.967
2022-03-01
IEEE Transactions on Power Electronics
Abstract:Compatibility issues with irregular current injection islanding detection methods are actually the problem that some irregular currents at the same frequency injected into the same line may cancel each other out and then the islanding detection may be impaired, which have been discussed under direct couple conditions (i.e., conditions without grid-connected transformers) in the literature. This article analyzes the issues under the opposite conditions where distributed generation (DG) units are equipped with grid-connected transformers, and is aimed at finding a solution. The analysis derives the setting formulas of key parameters for both three-phase and single-phase DG units, and shows that considering fault tolerance and practicability, only specific frequencies can be used for irregular currents. The usable frequencies are different under different cases. These conclusions are different from those based on direct couple conditions. By summarizing the conclusions based on conditions with grid-connected transformers achieved in this article and those based on direct couple conditions in the literature, a complete solution to compatibility issues is obtained. The conclusions in this article have been verified by the experiments and simulations at the end of this article.
engineering, electrical & electronic