Response Mechanism of DFIG to Transient Voltage Disturbance Under Commutation Failure of LCC-HVDC System

Zixuan Zheng,Jie Ren,Xianyong Xiao,Chunjun Huang,Yang Wang,Qi Xie
DOI: https://doi.org/10.1109/tpwrd.2020.3005720
IF: 4.825
2020-12-01
IEEE Transactions on Power Delivery
Abstract:Commutation failure is one of the common faults in the line commutated converter high voltage direct current (LCC-HVDC) transmission system, which will lead to a transient voltage disturbance with the characteristic of "decrease first and then increase" at the feed end. Such a transient voltage may cause severe dynamic responses on the wind generator adjacent to the converter station, resulting in the tripping of large-scale wind turbines and even cascading failure. By analyzing the principle of the transient voltage, this paper investigates the response mechanism of doubly-fed induction generator (DFIG), involving the variation of electrical parameters and fault ride through (FRT) ability. Further verifications through simulations and experiments prove that under the disturbance of commutation failure, DFIG may suffer greater transient shocks compared to a single sag or swell disturbance event. Finally, some suggestions are put forward to mitigate the transient voltage and improve the transient response of DFIG.
engineering, electrical & electronic
What problem does this paper attempt to address?
The paper attempts to address the issue of transient voltage disturbances caused by commutation failures in Line Commutated Converter High Voltage Direct Current (LCC-HVDC) systems and their impact on Doubly-Fed Induction Generators (DFIG). Specifically, the paper analyzes how this particular type of transient voltage disturbance affects the dynamic response of DFIGs, including changes in electrical parameters and Fault Ride Through (FRT) capability. Through simulations and experiments, it is verified that the transient impact on DFIGs caused by commutation failure disturbances can be more severe than single voltage dips or voltage rise events. Finally, the paper proposes some recommendations to mitigate transient voltage and improve the transient response of DFIGs. The main research background of the paper is that with the increasing demand for long-distance transmission between large wind farms and load centers, HVDC transmission has gradually become an important method for large-scale wind power transmission. However, due to the closer coupling of HVDC system terminals, the possibility of commutation failures caused by anomalies in the DC control system or faults in the receiving end AC power system increases, especially in LCC-HVDC systems. Commutation failures can cause a "first drop then rise" transient voltage disturbance at the feeding end, which may trigger severe dynamic responses in wind turbines near the wind farm, even leading to large-scale wind turbine tripping and cascading failures. Therefore, studying the response mechanism of DFIGs under such transient voltage disturbances is of great significance for improving the grid connection stability of wind farms.