Quantifying leaks from Schrader valves in air conditioning systems
Theresa Pistochini Robert McMurry 1 Engineering Manager,University of California,Davis,CA,USA2 Research and Development Engineer,University of California,Davis,CA,USA
DOI: https://doi.org/10.1080/23744731.2024.2370218
2024-07-26
Science and Technology for the Built Environment
Abstract:Refrigerants are a critical component of air conditioning and heat pump systems, but their high global warming potential has led to increasing concerns about their environmental impact. This research quantifies leakage from Schrader valves commonly used in air conditioning equipment. These valves serve as access points for refrigerant circuits and are often cited by service technicians as a source of leaks, contributing to greenhouse gas emissions. The study conducted laboratory testing of Schrader valves using an innovative experimental apparatus that tracked pressure and temperature of nitrogen gas contained by the valve over a 64-h test. The study found that 8 out of 61 used Schrader valves tested leaked at rates that would result in substantial refrigerant loss ( M = 1,280 g/yr, SD = 3,168 g/yr, range = 9.4 to 9,117 g/yr). Gasketed caps were found to prevent refrigerant loss. Combining a Schrader valve with a gasketed cap significantly reduces the risk of leaks, and their use should be encouraged in air conditioning systems. The methodology developed for estimating leak rates from Schrader valves could be applied to other components in refrigeration systems, contributing to more comprehensive efforts to reduce refrigerant emissions.
engineering, mechanical,construction & building technology,thermodynamics