Transient stability analysis between SG and grid-forming VSCs with current saturation control considering backward-swing dynamics

Yicheng Xue,Zheren Zhang,Guoteng Wang,Wentao Liu,Zheng Xu
DOI: https://doi.org/10.17775/CSEEJPES.2023.04260
IF: 6.014
2024-01-01
CSEE Journal of Power and Energy Systems
Abstract:This paper analyzes the transient angle stability between synchronous generators (SGs) and grid-forming voltage source converters (GFM-VSCs) considering backward-swing dynamics. The impact mechanism of current saturation control (CSC) on the backward-swing and forward-swing stability is addressed. Based on the second-order rotor motion equation, the conventional energy-based method for transient stability evaluation becomes rough driven by the interactions between SG and GFM-VSC. To overcome the barrier, a forward-time integral (FTI) method is proposed for calculating the critical clearing time (CCT). We discover that the CSC can affect the stable and unstable equilibrium points of the post-fault system, leading to both the backward-swing and forward-swing synchronism instability. Based on the mechanism, an enhanced synchronization control (ESC) is proposed. It combines a modified frequency control with a current-limit strategy to avoid backward-swing instability while enhancing forward-swing stability. Time-domain simulation verifies the theoretical analysis as well as the effectiveness and robustness of the proposed ESC.
What problem does this paper attempt to address?