A Measurement Method for Grid Impedance and Wind Farm Impedance under Background Harmonic

Min Zhang,Teng Xue,Xiong Du,Junliang Liu,Huipeng Li,Jinhao Wang,Chang Xiao
DOI: https://doi.org/10.1109/cieec60922.2024.10583657
2024-01-01
Abstract:The output impedance of wind farm is an important parameter to determine its small-signal stability. In this paper, the influence of background harmonics on impedance measurement at common coupling points of wind farm is analyzed. The results show that amplitude of the background harmonics affect the accuracy of the measurement. Thus, to overcome the influence, an impedance measurement method is proposed by adjusting the injected current amplitude. Then, grid impedance and wind farm impedance are obtained. The simulation results verify the feasibility and performance of the proposed method. It shows that the proposed method can accurately measure the impedance amplitude and impedance angle for the wind farm and grid impedance.