Analysis of Factors Affecting the Adhesion of 220kv Vertical Double Split Conductors

Jiankun Zhao,Xintao Wang,Baofeng Yan,Liming Wang
DOI: https://doi.org/10.1109/cieec60922.2024.10583748
2024-01-01
Abstract:Aiming at the adhesion problem of 220kV vertical double-split conductors, a critical load calculation model for double-split conductor adhesion was established, and the effects of gear distance, conductor split spacing, wind speed, wind vibration, conductor temperature difference, etc. on conductor adhesion were studied. The results show that the main cause of conductor adhesion is that the distance between the sub-conductors is too small due to wind vibration, construction errors, temperature differences between the upper and lower sub-conductors, etc. Under large load current conditions, the electromagnetic attraction between the sub-conductors causes adhesion. For a 220kV conductor-bonded line in Inner Mongolia, treatment measures were proposed to replace suspension clamps and increase the distance between conductor splits. The actual engineering treatment cases have achieved good results and provide reference for preventing similar problems.