Seamless Switching Control under Virtual Synchronous Generator Strategy for Electric Energy Router

Kaihua Zhang,Minghao Zheng,Jingfeng Wang,Xiaoqiang Zhou,Kainan Chen,Liqiang Yuan
DOI: https://doi.org/10.1109/aeees61147.2024.10544546
2024-01-01
Abstract:Electric energy router(EER) is an essential device in the new distribution network, featuring multiple voltage levels and multiple ports. This paper focuses on the switching control strategy for the grid-connected AC port of EER. As the connected distribution grid is considered a weak grid, the VSG control strategy is employed for the AC port in grid-connected mode. Similarly, in off-grid mode, the AC port also adopts the VSG control strategy to ensure consistency between the two modes. The grid-islanding process under VSG control inherently exhibits a smooth transition, while the grid-connecting process may cause large voltage and current stresses. To ensure a smooth grid connection, this paper proposes a pre-synchronization control strategy based on a predefined coordinate system without a phase-locked loop(PLL), and the feasibility of the control strategy is verified through simulations.
What problem does this paper attempt to address?