Energy Savings of Commercial Kitchen Ventilation and Air Conditioning Systems Based on Cooking Oil Control and Thermal Comfort

Chengquan Zhang,Fan Yang,Huan Liu,Yunfei Xia,Lianjie He,Yanlei Yu,Lingjie Zeng,Changsheng Cao,Jun Gao
DOI: https://doi.org/10.1016/j.enbuild.2024.114317
IF: 7.201
2024-01-01
Energy and Buildings
Abstract:To analyze the energy-saving potential of commercial kitchen ventilation and air-conditioning (VAC) systems and to create a good kitchen environment, this paper calculates the key influential parameters of the exhaust air volume and air supply temperature through CFD simulation. The former depends on the fume control effect and is closely related to the make-up air method, while the latter is governed by the thermal comfort. The energy consumption under different operational strategies is calculated using EnergyPlus. The following conclusions were obtained: (1) By summing the demand exhaust rate of the cookers with that of the fume hoods during the operation of multiple cookers, the pollution control effect can still be satisfied. Moreover, the airflow can be reduced by 20% through airflow optimization. (2) During summer, the conditioned airflow should constitute 30% of the total make-up air volume, with an air supply temperature of 22 ℃. Conversely, in winter, the conditioned airflow should comprise 40% of the total make-up air volume, with an air supply temperature of 14 ℃. (3) It is advisable to use a personalized conditioned air supply to create a local thermal environment, effectively reducing the energy consumption of ventilation and air conditioning systems. The energy-saving rates achieved through airflow optimization and on-demand ventilation are 51% and 71%, respectively.
What problem does this paper attempt to address?