Abstract:Stealthy attacks manipulate the operation of Industrial Control Systems (ICSs) without being undetected, allowing persistent manipulation of system operation and thus the potential to cause destructive damage. This paper introduces a new vulnerability of ICS that can be exploited to mount stealthy attacks without requiring any domain knowledge. This vulnerability is caused by a common practice in system monitoring, i.e., the SCADA monitors ICS operation at a much lower frequency than system execution, causing a loss of precision when the SCADA tries to cross-validate the issued control commands using the collected sensory data. Exploiting this vulnerability, an attack called <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">PLC-SAGE</i> is designed to stealthily manipulate the system operation by identifying and injecting malicious control commands that will not be concluded as abnormal by the SCADA. This paper further discusses a preferred ICS engineering practice and an attestation strategy to mitigate the above vulnerability and protect ICS from <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">PLC-SAGE</i> . Both <italic xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">PLC-SAGE</i> and the proposed mitigations have been experimentally validated on two ICS platforms.