Partial Discharge Localization Method in Transformer Based on Dissolved Gas Diffusion Inversion

Heli Ni,Ao Huang,Lin He,Xianqin Deng,Qingzhe Zhu,Zhicheng Wu,Qiaogen Zhang
DOI: https://doi.org/10.1109/apet59977.2023.10488932
2023-01-01
Abstract:Partial discharge (PD) is a common problem in transformer insulation systems, leading to the degradation of the insulation performance and even equipment failure if not handled properly. So accurately locating the source of partial discharge is of great significance to understand the condition of the transformer and take corresponding measures. Conventional methods for locating PD rely on detecting the ultrasonic or electromagnetic signals generated by PD, but these methods are often affected by the complex internal structure of the transformer, making it a challenging task. Based on the dissolved gas generated by PD, this study proposes a PD localization method based on dissolved gas diffusion inversion. The dissolved gas dynamic diffusion model is established to determine the diffusion coefficient of the characteristic gas generated by PD. The layout strategy of dissolved gas sensors was discussed, and the positioning with transformer partial discharge was successfully achieved using the weighted centroid algorithm, and the positioning error remained 10%. This study provides an alternative approach for localizing PD in oil-immersed power transformers.
What problem does this paper attempt to address?