Reasonable Temperature Differences for Each Stage and Heat Transfer Between Air and Water in Multi-Stage Air Treatment System

Wentao Wang,Chenjiyu Liang,Xianting Li
DOI: https://doi.org/10.1016/j.apenergy.2024.123140
IF: 11.2
2024-01-01
Applied Energy
Abstract:Compared to traditional air conditioning systems, the multi-stage air treatment system has a higher energy efficiency by using lower grade energy, but the reasonable temperature differences for each stage (Delta tstage) and heat transfer between air and water (Delta ttrans) needed to ensure an efficient system design remain unclear. To obtain the reasonable Delta tstage and Delta ttrans values required to maximize the energy efficiency of the multi-stage air treatment system, mathematical models are established to calculate the system's energy consumption. Six representative climate zones, two operating modes, and several working conditions are selected to evaluate the effects of different Delta tstage and Delta ttrans values on the performance of the multi-stage air treatment system. Reasonable Delta tstage and Delta ttrans values are obtained by minimizing the energy consumption of the system. The results show that: (1) the difference in reasonable Delta tstage and Delta ttrans under the different conditions is small, and it is possible to have a unified reasonable Delta tstage and Delta ttrans. (2) In the cooling season, the reasonable Delta tstage and Delta ttrans values are 6-8 and 4-5 degrees C, respectively; in the heating season, these values are 10-12 and 5-7 degrees C, respectively. (3) Compared to the traditional system, the maximum and annual average energy-saving rates of multi-stage air treatment system in an office building in Beijing are 34.5% and 17.9%, respectively. This study's results provide a solid foundation for building multi-stage air treatment system.
What problem does this paper attempt to address?