Field Testing of Air Change Rate in University Dormitories under Different Window-Opening Behaviors in Nanjing , China

Xiangnan Qiu,Weihui Liang
DOI: https://doi.org/10.26868/25222708.2023.1593
2023-01-01
Abstract:Air change rate per hour (ACH) is essential for assessing building performance, reflecting indoor air quality (IAQ), and calculating energy consumption. In China, research has mostly focused on spaces such as residences and offices, with less research and data on dormitories. Therefore, a field measurement using the CO2 decay method was conducted on university dormitories in Nanjing during the winter of 2018-2020, and 58 valid samples were obtained. Since different window-opening behaviors have a significant impact on ventilation, ACH was tested under open and closed window conditions. ACH under closed-window conditions ranged from 0.08 to 1.11 h-1 with a median value of 0.41 h-1. ACH under open-windows conditions ranged from 1.07 to 15.15 h-1 with a median value of 3.77 h-1. ACH in both states follows a log-normal distribution. This analysis can be used to assess the current state of ventilation in the dormitories, analyze the impact of window-opening behavior on ventilation, and provide data for IAQ improvements and energy savings.