Transmission line frequency-domain fault location method based on the phasor-time space curve characteristics that considers decaying DC deviation
Yuansheng Liang,Jiayan Ding,Haifeng Li,Gang Wang,Zihong Zhang
DOI: https://doi.org/10.1016/j.ijepes.2022.108308
2022-11-01
Abstract:To improve the accuracy of frequency-domain fault location methods, finding new fault features in a limited fault data window is the most effective means. Different from the existing methods by eliminating decaying DC (DDC), this paper makes use of the DDC deviation phasor in the DFT output phasors. With the sliding of the DFT time window, the output phasor of two-terminal voltage difference function at different calculated points of the line has the following features: the actual fault point presents the characteristic of phase-time space curve with exponential attenuation in the same plane, but the farther the non-fault point is from the actual fault point, the more it deviates from this characteristic. Based on the feature difference, this paper uses the space curve fitting degree as the evaluation index of fault point characteristic, and constructs a new fault location criterion of frequency-domain method. Finally, electromagnetic transient fault simulation is used to test the proposed method and its comparison test, and the high performance of the proposed method is validated by simulations.
engineering, electrical & electronic