Optimization of Indoor Temperature Sensor Deployment in Large Spaces for Multiple Building Operation Scenarios Using the Genetic Algorithm

Mufeng Yuan,Yang Geng,Borong Lin,Hao Tang,Yuren Yang
DOI: https://doi.org/10.1016/j.jobe.2024.110446
IF: 7.144
2024-01-01
Journal of Building Engineering
Abstract:Indoor Environmental Quality (IEQ) monitoring is significant for occupant comfort and system operation. Due to the complicated nature of the indoor environment, large spaces generally require an appropriate sensor deployment scheme for scientific, comprehensive, and costeffective IEQ monitoring. However, most sensor deployment methods rely on manual experience without quantitative guidance. This study develops an optimization method for sensor deployment in large spaces by selecting air temperature as the targeted IEQ parameter. Three typical operation scenarios are considered separately and simultaneously for sensor deployment optimization. The effectiveness of the method has been demonstrated in an airport terminal. The results indicate that the proposed method outperforms the traditional methods in all scenarios. For each scenario, 20-30 (one per 300-450 m2) 2 ) is the appropriate deployed number due to the marginal benefit decrease of additional sensors. Optimal deployed locations exhibit similarities and contradictions in different scenarios and trade-offs are required in a multi-objective optimization.