Multi-parameter optimization of mixed refrigerant circulation system in natural gas light hydrocarbon removal system

LI Kai-yu,ZHONG Wei,LI Jian-gang,YAN Zhi-qiang,CHEN Ying,CAO Gai-yu,LIU Gui-lian
DOI: https://doi.org/10.19909/j.cnki.ISSN1009-0045.2023.06.0448
2023-01-01
Abstract:In order to reduce the energy consump-tion in the refrigeration device area and ensure that the maximum heat transfer temperature difference of the main cold box was lower than 25.00℃,the chemical steady-state process simulation software Aspen Hysys V10 was used to model the mixed re-frigerant circulation cooling(MRC)system of the 10.9 kt/a natural gas light hydrocarbon removal unit of Oil and Gas Co Ltd of Changqing Oilfield(Yulin),PetroChina,and the cold-heat compound curve of the main cold box was constructed after simulation.Then the multi-parameter sensitivity analysis and optimization were carried out.The re-sults showed that the optimal values of the tempera-ture of the refrigerant separator and the high-pres-sure refrigerant flow rate of the main cold box related to the key control parameters of the MRC system were 1.75℃ and 64 960.00 m3/h respectively,and the optimal inlet and outlet pressure of the refrigerant compressor were 270.00,2 940.00 kPa,respectively.Comparing with that before optimization,under the optimal operation conditions,the maximum heat transfer temperature difference in the main cold box was 23.47℃ by the decrement of 2.37℃,and the energy consumption in the refrigeration device area was 5799.17 kW by the reduction of 28.01%.