Dispatch Model for CHP with Pipeline and Building Thermal Energy Storage Considering Heat Transfer Process
Yuanhang Dai,Lei Chen,Yong Min,Qun Chen,Junhong Hao,Kang Hu,Fei Xu
DOI: https://doi.org/10.1109/tste.2018.2829536
IF: 8.31
2019-01-01
IEEE Transactions on Sustainable Energy
Abstract:Utilizing the flexibility provided by the thermal system components, for example, pipelines in the district heating network (DHN), building envelopes as well as thermal energy storage (TES) devices, can be an effective way for power system to solve the wind curtailment problem which closely relates to the limited flexibility of combined heat and power. However, almost all the previous studies ignored heat transfer (HT) constraints when modeling these abovementioned thermal system components. An HT constraint is one of the most important constraints in thermal system analysis, without considering it may result in infeasibility for the dispatch results. Hence, in this study, we propose a detailed model for these three components, namely DHN, building envelopes, and TES devices, with consideration of HT constraints. This model can be further simplified to consider different combinations of these components by setting relevant model parameters. An iteration solution to deal with such nonlinear HT constraints is put forward. The effectiveness of the proposed model is verified by case studies. The simulation results demonstrate that considering HT constraints is necessary when try to exploit the flexibility provided by these thermal system components, or we may overestimate their benefit.