A Protection Scheme for Flexible Low Frequency AC System Power Collecting Line of Offshore Wind Farm Based on Transient High Frequency Energy

Xing Gao,Tianjia Sun,Tonghua Wu,Gang Yao,Yangyang He,Nengling Tai
DOI: https://doi.org/10.1109/icpre59655.2023.10353606
2023-01-01
Abstract:Flexible low-frequency AC (FLAC) technology uses frequencies of 20Hz or 16.7Hz to transmit power electricity, demonstrating significant advantages in terms of economy and transmission capacity, and has broad prospects for application in offshore wind power transmission systems. In the FLAC system of offshore wind power, the two ends of the collection line are connected to wind power and low-frequency conversion equipment, and the fault characteristics exhibit typical weak feedback characteristics, which can easily lead to the failure of traditional protection principles based on power frequency. To address this issue, this paper proposes a new protection scheme for power collecting line based on transient high-frequency energy. When a fault occurs, the fault component of voltage and current is first extracted, then the high-frequency component is extracted to calculate the transient high-frequency energy, thus achieving the discrimination of internal fault and external fault. A simulation model of FLAC system is established on the PSCAD/EMTDC simulation platform. The simulation results show that this scheme can accurately identify faults and has good resistance to fault resistance. The protection scheme is helpful to ensure the safe and reliable operation of FLAC power transmission system.
What problem does this paper attempt to address?