Analysis of Optimum State of Medial Liquid Injection Circulatory System for the Refrigerated Display Cabinet

Yang Shen
2004-01-01
Abstract:The refrigerated display cabinet is taken as an example to study,the optimum intermediate state of medial liquid injection circulatory system with the scroll compressor.Then the changing regularity of optimum intermediate pressure is researched in the condition of different condensing temperature or different evaporating temperature.Further,the optimum intermediate pressure and the COP under optimum intermediate pressure between R22 and R407c in the same condition are compared.The conclusion shows that it is available to use R407c replacing R22,and performance of two refrigerants keeps same basicalling.