Condensation Heat Transfer Enhancement Study of R22,R410A,R407C and R134a on a Bundle of Petal-Shaped Finned Tubes

Zhengguo Zhang
2011-01-01
Abstract:Condensation heat transfer characteristics of R22,R410A,R407C and R134a on Bundle of Petal-shaped finned tubes are experimentally investigated.Experiments were carried out at saturation temperatures of 35℃and 39℃and wall subcoolings from 3 to 8℃.The results revealed that the average condensation heat transfer coefficients at 35℃are higher than those at 39℃.Contrary to non-azeotropic R407C,the average condensation heat transfer coefficients of R22,R410A,and R134a decrease as the wall subcooling increase.For tube bundle,the HCTs decrease from the top to the bottom tube under a given wall subcooling.
What problem does this paper attempt to address?