Experimental investigation on the condensation heat transfer coefficient and frictional pressure drop of R-513A and R-134a in commercial refrigeration tubes
Thana Arkadumnuay,Stephen Manova,Witsawat Leunanonchai,Lazarus Godson Asirvatham,Somchai Wongwises
DOI: https://doi.org/10.1016/j.ijheatmasstransfer.2024.125735
IF: 5.2
2024-05-29
International Journal of Heat and Mass Transfer
Abstract:An experimental investigation to determine the average heat transfer coefficient (h av ) and frictional pressure drop (ΔP F ) characteristic of R-513A and R-134a in a smooth tube (ST) and micro-fin tube (MFT) is carried out. A 2500 mm long counter-flow tube-in-tube heat exchanger made of copper is used for conducting experiments. The ST and MFT with inner diameters (D i ) of 6.74 and 6.82 mm, respectively, are experimentally tested for various operating conditions such as saturation temperatures (T sat = 40 to 50 °C), heat fluxes (q" =9.8 to 19.6 kW/m 2 ), mass fluxes ( G = 575 to 770 kg/m 2 s) and average vapor qualities (x av = 0.2 to 0.9). The influence of q", G, and T sat on h av and ΔP F are discussed. First, a comparison between R-513A and R-134a in an ST showed maximum reductions of 16 and 20 % in h av and ΔP F, respectively for R-513A, when compared to R-134a. Second, the MFT, due to its higher heat transfer area, resulted in 69 % and 120 % enhancements in h av and ΔP F , respectively, compared to that of an ST. Hence, the findings of this research provide information that is currently useful to the thermal industries, affirming that R-513A can be a suitable long-term alternative refrigerant.
engineering, mechanical,thermodynamics,mechanics