A Detection Based on OMES and MTAD-GAT for False Data Injection Attack in Smart Grid

Huifeng Li,Tiecheng Li,Tianying Chen,Guangxuan Zhao,Yixiao Zhu,Xiangxing Kong
DOI: https://doi.org/10.1109/EI256261.2022.10117053
2022-01-01
Abstract:The false data injection attack (FDIA) is a new attack method aiming at power system state estimation. A successful FDIA can avoid the traditional bad data detection (BDD) and falsify measurements without detection. As a result, the dispatching center makes wrong decisions threatening safe and stable power system operation. A detection based on model-driven and data-driven methods is proposed. Optimal measurement equipment scheduling (OMES) is model-driven to calculate score 1 at each timestamp. Multivariate time-series anomaly detection via graph attention network (MTAD-GAT) is data-driven to get scores 2 and 3. The three scores above calculate the final inference score, which can maximize the overall effectiveness of FDIA detection. Timestamp can be identified as attacked if its final score is larger than a threshold chosen by Peak Over Threshold (POT) automatically. With the coordination of MTAD-GAT, OMES performs better detecting FDIA than the Support Vector Machine-Gabor Transform (SVM-GAB) method and Extreme Gradient Boosting (XG-Boost) method validated by simulations on the IEEE 14-bus system.
What problem does this paper attempt to address?