Reliability analysis of phase differential protection for PV outgoing circuit fault

D. Yang,H. Yang,K. Chen,H. Shi,M. Shi,H. Cheng,X. Zheng,N. Tai
DOI: https://doi.org/10.1049/icp.2023.2219
2023-01-01
Abstract:In the photovoltaic connected distribution system, the photovoltaic is connected to the AC grid through the inverter. It brings great challenges to the protection of the AC outgoing line. When a fault occurs on the AC side, the fault current phase presents a controlled characteristic. The control mode of the inverter has great influence on the fault current, and the negative sequence current suppression of the inverter will further affect the fault current phase. Differential protection mainly uses the current and phase relationship between photovoltaic side and grid side for fault discrimination. Due to the large difference in fault current between photovoltaic side and grid side, it is difficult to ensure reliable operation of differential protection. This paper aims at the scenario of photovoltaic connecting to AC power grid. The phase characteristics of photovoltaic side current are analyzed with inverter control mode. The differential protection sensitivity in this scenario is analyzed by simulation.
What problem does this paper attempt to address?