A novel distance protection for phase-to-phase short-circuit fault on AC collection line in VSC-HVDC system with offshore wind farm integration based on measured impedance correction

H. Zhang,X. Zheng,Z. Liu,H. Liu,H. Ye,Q. Gui,C. Lan,C. Chao,Y. Xie,N. Tai
DOI: https://doi.org/10.1049/icp.2023.2169
2023-01-01
Abstract:Nonlinear fault response of power electronics poses challenges to the reliability of protection. As the power electronic converters being connected to both ends of the AC collection line in the VSC-HVDC system with offshore wind farm integration, the fault characteristics of the AC collection line has completely changed, and the adaptability of protection is seriously affected. Distance protection is not reliable enough to endure the fault resistance due to the fault current characteristics in amplitude and phase angle on AC collection line. When a phase-to-phase short-circuit occurs with fault resistance, the distance protection has the worst performance. To address this problem, the fault characteristics of AC collection line in VSC-HVDC system with offshore wind farm integration are analysed to establish the relationship between measured impedance and fault line impedance for phase-to-phase short-circuit fault. Based on measured impedance correction, a novel distance protection scheme for phase-to-phase short-circuit on the AC collection line in VSC-HVDC system with offshore wind farm integration is proposed. The correctness and effectiveness of the proposed protection scheme are verified through simulations based on PSCAD/EMTDC.