Hygienic Evaluation on Centralized Air Ventilation System During Operation in a Foreign-Related Hotel in Shenzhen City

Yan Ya
2014-01-01
Abstract:[Objective]To investigate the sanitary status of centralized air ventilation system in a foreign-related hotel in Shenzhen City,provide the technical basis for strengthening the hygiene management. [Methods]According to the Hygienic supervision measures on centralized air ventilation system in public places,the centralized air ventilation system was detected and evaluated. [Results]The qualification rate of PM10,total bacterial count,total fungi count and β-hemolytic streptococcus in sending outlet was 100. 0%,80. 0%,86. 7% and 100. 0%,respectively. The qualification rate of dust amount,total bacterial count,total fungi count and β-hemolytic streptococcus on surface of ventilation pipes was 100. 0%,100. 0%,53. 3% and 100. 0%,respectively. The qualification rate of Legionella pneumophila in cooling water and condensed water was 100. 0%.[Conclusion]There is a certain degree of contamination in the centralized air ventilation system of this foreign-related hotel,and the hygiene management should be strengthened.