Reactive Energy Measurement of Three-Phase Three-Line System under Non-Sinusoidal and Asymmetry Condition

Yongqiang Liu
2008-01-01
Abstract:This paper introduces the measurement technology of sinusoidal reactive energy and its limitation,and investigates the non-sinusoidal reactive power theory and advanced electronic measurement technology of reactive energy measurement importantly.Then puts forward a new three-phase instantaneous reactive power theory based on Akagi's instantaneous reactive power theory,and realizes the reactive energy measurement of three-phase three-line system Under Non-sinusoidal Condition with FFT analysis.This method is used for electric energy metering device of fundamental wave and harmonics of three-phase three-line system Under Non-sinusoidal Condition,which gets good effects.
What problem does this paper attempt to address?